Solenoid Valves in Industrial Automation: Types, Functions and Selection Criteria

— A Practical Guide for Engineers, EPCs, and Project Teams

The solenoid valve is one of the most ubiquitous yet least understood components in industrial automation. It is the small device that sits between the control system and the actuator, converting an electrical signal into a pneumatic or hydraulic switching action. Without it, the control valve cannot open, the cylinder cannot stroke, and the emergency shutdown system cannot isolate the process.

Despite its apparent simplicity, the solenoid valve is also one of the most common sources of failure in pneumatic control systems. A wrong voltage, an undersized orifice, an incompatible seal material, or an incorrectly wired coil can cause a control valve to fail in the wrong direction—or not to respond at all. The solenoid valve is small, but its consequences are not.

This guide explains the types, functions, and selection criteria for solenoid valves in industrial automation, with practical guidance for engineers, EPCs, and project teams.


1. What Is a Solenoid Valve?

A solenoid valve is an electromechanically operated valve. It uses a solenoid—a coil of wire that generates a magnetic field when energised—to move a plunger or armature, which opens or closes one or more flow paths.

Core components:

ComponentFunction
Coil (solenoid)Generates magnetic force when energised
Plunger / armatureMoves in response to the magnetic force
Seal / diaphragm / discOpens or closes the flow path
BodyHouses the flow path and connections
SpringReturns the plunger to its de-energised position
OrificeThe flow passage through the valve

Basic operation: When the coil is energised, the magnetic force pulls the plunger against the spring, opening (or closing) the valve. When de-energised, the spring returns the plunger, reversing the action.


2. Why Solenoid Valves Matter

In industrial automation, solenoid valves serve three critical functions:

FunctionDescription
Pilot controlSends an air signal to the actuator to open or close a control valve
Fail-safe actionDetermines the valve's fail-safe position (FO, FC, or FL) on signal or power failure
On/off controlDirectly controls the flow of gas, liquid, or air in on/off applications

Key insight: In a pneumatic control valve assembly, the solenoid valve is often the single point of failure for the valve's fail-safe response. If the solenoid fails to de-energise, the valve will not fail to its safe position—regardless of the actuator's spring design.


3. Types of Solenoid Valves

Solenoid valves are classified by several criteria: the number of ports, the operating principle, the de-energised state, and the application.

3.1 Classification by Number of Ports

TypePortsFunctionTypical Application
2-way2On/off control of flow (inlet and outlet)Shut-off service, isolation
3-way3Diverts or mixes flow; often used to exhaust an actuatorPilot valve for single-acting actuators
4-way4Controls a double-acting actuator (extend/retract)Double-acting cylinders
5-way5Controls a double-acting actuator with separate exhaustDouble-acting cylinders with independent exhaust

2-way solenoid valves are the most common for shut-off and isolation service. 3-way valves are common for piloting single-acting actuators. 4-way and 5-way valves are common for double-acting actuators.

3.2 Direct-Acting vs Pilot-Operated

TypeOperating PrincipleAdvantagesLimitations
Direct-actingThe coil directly moves the plunger against the process pressureWorks at zero pressure differential; simple; reliableLimited flow capacity; requires higher coil power
Pilot-operatedThe coil opens a small pilot orifice, which uses process pressure to open the main valveHigh flow capacity; lower coil powerRequires minimum pressure differential to operate
Semi-directCombines direct and pilot operationHigh flow at low pressure differentialMore complex; higher cost

Selection principle: Use direct-acting for low-pressure or zero-differential applications. Use pilot-operated for higher flow rates where a minimum pressure differential is always available.

3.3 Normally Closed (NC), Normally Open (NO), and Universal

ConfigurationDe-energised StateEnergised StateTypical Application
Normally Closed (NC)ClosedOpenFail-safe shut-off; most common
Normally Open (NO)OpenClosedFail-safe relief; cooling water
Universal (bi-stable)Holds last positionHolds last positionLatching applications; power saving

Critical: The NC/NO designation refers to the de-energised state. For fail-safe design, the solenoid configuration must match the valve's required fail-safe position (see Section 6).

3.4 Classification by Application

TypeApplication
Pilot solenoid valveControls air to a pneumatic actuator
Process solenoid valveDirectly controls process fluid (gas, liquid, steam)
Safety solenoid valveSIL-rated for ESD and SIS applications
High-pressure solenoid valveHydraulic and high-pressure gas service
Low-power solenoid valveBattery-powered or solar-powered applications
Explosion-proof solenoid valveHazardous area applications (Ex d, Ex ia, Ex e)

4. Key Functions of Solenoid Valves

4.1 Pilot Control of Pneumatic Actuators

The most common function of a solenoid valve in industrial automation is to pilot a pneumatic actuator. The solenoid valve supplies or exhausts air to the actuator in response to a control signal.

For a spring-return actuator:

  • Energise to open: Solenoid supplies air; spring closes on de-energisation

  • Energise to close: Solenoid exhausts air; spring opens on de-energisation

For a double-acting actuator:

  • 4-way or 5-way solenoid directs air to one side of the piston while exhausting the other

4.2 Fail-Safe Action

The solenoid valve determines the valve's fail-safe response on loss of power or signal.

Valve Fail PositionSolenoid ConfigurationAction on De-energisation
Fail Closed (FC)NC solenoid, air-to-open actuatorExhausts air; spring closes valve
Fail Open (FO)NO solenoid, air-to-close actuatorExhausts air; spring opens valve
Fail in Place (FL)Universal or lock-up valveTraps air; valve holds position

Critical: The solenoid valve must be configured so that de-energisation results in the safe position. This is the fundamental principle of fail-safe design.

4.3 On/Off Control of Process Fluid

In some applications, the solenoid valve directly controls the process fluid—not just pilot air.

ApplicationSolenoid Type
Gas shut-off2-way NC, high-pressure
Liquid dosing2-way NC, corrosion-resistant
Steam injection2-way NC, high-temperature
Sample switching3-way, multi-port

4.4 Emergency Shutdown (ESD)

In safety instrumented systems, solenoid valves are used to trip final elements to their safe position.

RequirementSpecification
SIL ratingSIL 2 or SIL 3 per IEC 61508/61511
De-energise to tripSolenoid de-energises on ESD signal
Proof testPartial stroke test capability
DiagnosticsSolenoid health monitoring
Response timeFast stroking, typically <2 seconds

5. Selection Criteria

5.1 Valve Function

RequirementSelection
On/off shut-off2-way NC or NO
Diverting or mixing3-way
Double-acting actuator4-way or 5-way
Pilot control3-way (single-acting) or 4/5-way (double-acting)

5.2 Flow Capacity (Cv/Kv)

The solenoid valve must have sufficient flow capacity to operate the actuator within the required time.

ParameterConsideration
Actuator volumeLarger actuators require higher Cv
Stroking timeFaster stroking requires higher Cv
Supply pressureHigher pressure requires lower Cv
Pressure dropAcceptable pressure drop across the solenoid

Sizing principle: Calculate the required Cv based on actuator volume, stroke time, and supply pressure. Select a solenoid with Cv equal to or greater than the calculated value.

5.3 Pressure and Temperature

ParameterConsideration
Maximum operating pressureMust exceed the maximum process pressure
Minimum operating pressurePilot-operated valves require minimum differential
Temperature rangeMust cover the process and ambient temperature
Pressure differentialDirect-acting works at zero differential; pilot-operated requires minimum differential

5.4 Voltage and Power

ParameterCommon Options
Voltage24V DC, 110V AC, 220V AC
Power2W to 20W (typical)
Duty cycleContinuous or intermittent
Power consumptionLow-power options for battery/solar applications

Selection principle: Match the voltage to the available power supply. For ESD applications, 24V DC is standard. For low-power applications, specify low-wattage coils.

5.5 Body and Seal Materials

MaterialApplication
BrassWater, air, non-corrosive media
Stainless Steel (316L)Corrosive media, high-temperature, hygienic
AluminiumLightweight, non-corrosive
Plastic (PVC, PVDF)Highly corrosive media
NBR (Buna-N)Water, air, oil (standard)
FKM (Viton)High temperature, aggressive chemicals
EPDMSteam, hot water, polar solvents
PTFEExtreme chemical resistance

Selection principle: Match the body and seal materials to the process fluid. For corrosive media, use stainless steel or plastic bodies with PTFE or FKM seals.

5.6 Response Time

ApplicationTypical Response Time
ESD<2 seconds
Process control2–10 seconds
On/off control1–5 seconds
Fast cycling<1 second (special designs)

5.7 Explosion Protection

CertificationApplication
Ex dFlameproof enclosure for hazardous areas
Ex iaIntrinsically safe for Zone 0/1
Ex eIncreased safety for Zone 1/2
Ex nNon-incendive for Zone 2

Selection principle: Match the Ex certification to the area classification. For Zone 0/1, use Ex ia. For Zone 1/2, Ex d or Ex e.

5.8 SIL Rating

For safety instrumented functions, the solenoid valve must be SIL-rated.

SIL LevelApplication
SIL 1Low-risk safety functions
SIL 2Medium-risk safety functions
SIL 3High-risk safety functions (ESD, SIS)

Selection principle: Verify the SIL certificate covers the specific model and application. Consider redundant solenoids for SIL 3 applications.

5.9 Manual Override

OptionApplication
Manual operatorAllows valve operation during power failure
Push-button overrideTemporary manual operation
Lever overrideContinuous manual operation
Lock-out/tag-outSafety isolation

Best practice: Specify manual override for critical valves that may need to be operated during commissioning or maintenance.


6. Solenoid Valve and Fail-Safe Position

The solenoid valve is a key component in determining the fail-safe position of a control valve. The table below summarises the combinations.

Actuator TypeSolenoid TypeDe-energised ActionValve Fail Position
Spring-return, air-to-openNCExhausts airFail Closed
Spring-return, air-to-closeNOExhausts airFail Open
Double-actingUniversalTraps airFail in Place
Double-acting + lock-upNCTraps airFail in Place

Key principle: The solenoid valve must be selected so that de-energisation results in the safe position. In most industrial applications, the safe position is fail-closed, which requires an NC solenoid on an air-to-open actuator.

Common mistake: Using an NC solenoid on an air-to-close actuator. On de-energisation, the solenoid exhausts air, and the spring opens the valve—resulting in fail-open, not fail-closed. This is a potentially catastrophic error in safety-critical applications.


7. Common Applications

IndustryApplicationSolenoid Type
Oil & gasESD valve piloting3-way NC, Ex d, SIL-rated
ChemicalChemical dosing on/off2-way NC, PTFE seal
PowerSteam admission control2-way NC, high-temperature
Water treatmentPump start/stop2-way NC, brass body
Food & beverageSanitary on/off2-way NC, stainless steel, FDA seals
PharmaceuticalClean-in-place (CIP)2-way NC, stainless steel, PTFE
HVACChilled water control2-way NC, brass body
PackagingCylinder control4-way or 5-way

8. Common Mistakes to Avoid

MistakeConsequencePrevention
NC/NO configuration not matching fail positionValve fails in wrong directionVerify solenoid logic against cause-and-effect matrix
Undersized CvSlow valve stroking; ESD response too slowCalculate Cv based on actuator volume and stroke time
Incompatible seal materialSeal swelling; leakage; failureMatch seal material to process fluid
Incorrect voltageCoil burnout or no operationVerify supply voltage
No manual overrideCannot operate during power failureSpecify manual override for critical valves
No Ex certification for hazardous areaSafety incident; regulatory violationMatch Ex rating to area classification
No SIL rating for safety functionSafety function not reliableUse SIL-rated solenoid for ESD/SIS
Pilot-operated valve with insufficient pressure differentialValve does not openUse direct-acting or semi-direct for low differential
Duty cycle exceededCoil overheating; failureVerify duty cycle rating
No surge protectionCoil failure from voltage spikesAdd surge suppressor
Poor air qualitySolenoid contamination; stickingInstall filter regulator upstream
Incorrect orifice sizeInsufficient flow; slow responseSize orifice for the required Cv
No spare solenoidsExtended downtime if solenoid failsStock spare solenoids for critical valves

9. Applicable Standards

StandardScope
IEC 60534-1Industrial-process control valves—terminology
ISO 5599Pneumatic fluid power—five-port directional control valves
ISO 15407Pneumatic fluid power—directional control valves
IEC 60079Explosive atmospheres—equipment certification
IEC 61508 / IEC 61511Functional safety—SIL requirements
IEC 60529Ingress protection (IP code)
NEMA 4/4XEnclosure protection
API 553Refinery valves and accessories for control and safety systems
UL 429Electrically operated valves
CSA C22.2 No. 139Electrically operated valves

10. Why Choose Anhui Tiankang for Solenoid Valve Solutions?

Anhui Tiankang (Group) Co., Ltd. has nearly five decades of experience in industrial instrumentation and valve automation. We provide complete solenoid valve solutions for control valves, actuators, and safety systems.

Solenoid valve product portfolio:

ProductTypeKey Features
2-way solenoid valveNC/NO, direct-acting or pilot-operatedBrass or 316L SS; NBR, FKM, EPDM, PTFE seals
3-way solenoid valveNC/NO/universalFor single-acting actuators
4-way / 5-way solenoid valveDouble-acting actuatorsFor cylinder control
Ex-proof solenoid valveEx d, Ex ia, Ex eFor hazardous areas
SIL-rated solenoid valveSIL 2 / SIL 3For ESD and SIS applications
Low-power solenoid valve<2WFor battery or solar-powered applications
High-pressure solenoid valveUp to 1,000 barFor hydraulic and high-pressure gas service
Sanitary solenoid valve3A, EHEDGFor food and pharmaceutical applications

Accessories:

  • Manual override

  • Surge suppressor

  • DIN connectors

  • Cable glands

  • Mounting brackets

Core advantages:

  • Complete certifications: CCC Ex, ATEX, IECEx, SIL

  • CNAS-accredited laboratory: full performance testing

  • Engineering support: solenoid selection, Cv calculation, fail-safe verification

  • Long-term supplier to CNPC, Sinopec, CNOOC, and international EPC projects

  • One-stop supply: valves + actuators + positioners + solenoids + accessories


11. Conclusion

Solenoid valves are small components with large responsibilities. They determine whether a control valve opens or closes, whether an ESD system trips correctly, and whether a process can be shut down safely when something goes wrong.

Key takeaways:

Selection FactorKey Principle
Valve function2-way, 3-way, 4-way, or 5-way based on application
Operating principleDirect-acting for zero differential; pilot-operated for high flow
NC/NO configurationMust match the required fail-safe position
Cv/KvSize based on actuator volume and stroke time
MaterialsMatch body and seal to process fluid
VoltageMatch to available power supply
Ex certificationMatch to area classification
SIL ratingRequired for safety instrumented functions
Manual overrideRequired for critical valves
Response timeCritical for ESD applications

The most important rule: The solenoid valve must be selected so that de-energisation results in the safe position. In most industrial applications, this means an NC solenoid on an air-to-open actuator for fail-closed service. Verify this configuration at FAT, SAT, and commissioning.

Remember: A solenoid valve that fails in the wrong direction is worse than no solenoid valve at all. The solenoid is the last link in the control chain—and often the first to be blamed when a valve fails. Select it correctly, verify it thoroughly, and keep a spare on the shelf.


Contact Us

For solenoid valve selection, fail-safe verification, or project quotations, please contact:

Yin Shuangjie
International Sales Manager
📧 Email: [email protected]
📱 WhatsApp / Zalo: +86 17856068126
🌐 Website: http://www.tiankang-global.com/

Anhui Tiankang – Your partner for reliable solenoid valve and instrumentation solutions.